Solar Battery Bank Size Calculator

Work out the battery capacity that carries your loads through nights and cloudy spells without draining the bank too far. Choose the chemistry, the days of backup, and the lowest site temperature.

Reading Your Result

The nameplate watt-hours figure is the capacity printed on the battery, not the energy you can use. The formula divides by depth of discharge, efficiency, and a cold-weather factor to find how much label capacity you must buy.

Amp-hours depend on system voltage, so the same energy needs fewer amp-hours at 48 V than at 12 V. Pick the voltage first, then read the Ah result. If the bank looks huge, check the chemistry, since lead-acid needs about twice the label capacity of LiFePO4 for the same use.

How It's Calculated

Formula

Battery Wh = daily Wh × days ÷ (DoD × round-trip efficiency × temperature factor)

Nameplate capacity. LiFePO4 uses DoD 0.90 and efficiency 0.95. AGM and gel use 0.50 and 0.85. Flooded uses 0.50 and 0.80.
Formula

Lead-acid: 25°C = 1.00, 10°C = 0.90, 0°C = 0.80, −10°C = 0.70, −20°C = 0.60

Temperature factor. Values between these points are linear. LiFePO4 is 1.00 at 0°C or above and 0.85 below, and it must never charge below 0°C without heating.
Formula

Ah = battery Wh ÷ system V

Amp-hours. Round up to the next real battery size.

Worked Examples

Worked example · South Africa, load shedding backup

Daily use is 4,000 Wh, with 1 day of backup and LiFePO4 kept indoors at 25°C.

Divisor = 0.90 × 0.95 × 1.00 = 0.855.

Battery Wh = 4,000 × 1 ÷ 0.855 = 4,678 Wh.

At 48 V, 4,678 ÷ 48 = 97.5 Ah, so a 100 Ah 48 V battery is the match.

Worked example · Norway, unheated hut with flooded lead-acid

Daily use is 1,200 Wh with 2 days of backup, and the lowest temperature is −10°C, so the factor is 0.70.

Divisor = 0.50 × 0.80 × 0.70 = 0.28.

Battery Wh = 1,200 × 2 ÷ 0.28 = 2,400 ÷ 0.28 = 8,571 Wh.

At 24 V, 8,571 ÷ 24 = 357 Ah, so a 360 Ah bank works.

At −5°C the factor would sit halfway between 0.80 and 0.70, which is 0.75.

Common Mistakes

  • Reading nameplate Ah as usable Ah. Lead-acid gives about half, and draining it deeper shortens its life.
  • Ignoring cold. A bank sized at 25°C can fall short in a frosty shed.
  • Charging LiFePO4 below 0°C. It can cause permanent damage, so use a battery with a heater or keep it warm.
  • Mixing old and new batteries in one bank, which pulls the whole bank down to the weakest unit.

Frequently Asked Questions

How many days of autonomy should I choose?

One day suits grid-assisted or generator-backed systems. Two to three days suit full off-grid homes, and the right number depends on how long your cloudy spells last.

Why does LiFePO4 need less nameplate capacity?

It safely uses about 90 percent of its capacity and wastes less energy in the charge cycle. Lead-acid is usually limited to 50 percent for a long life.

What does the temperature factor do to a LiFePO4 bank?

It only applies below 0°C, where the factor is 0.85. Because charging below freezing is unsafe, the better fix is a heated or insulated battery.

Can I wire batteries in series or parallel to reach the number?

Yes, as long as they're identical and the system voltage matches your inverter and controller. Series adds voltage, and parallel adds amp-hours.

Is gel better than AGM?

They share the same planning numbers here. Gel often handles heat and deep cycles a little better, but it needs gentler charging.

Should the bank include a safety margin?

The depth of discharge limit is already the margin. Add capacity only for loads you expect to grow into.

Related Calculators and Guides