Reading Your Result
The continuous rating comes from the AC watts that run at once, plus a 25 percent margin. Add only what runs simultaneously. A load that never overlaps with the others doesn't need to be counted again.
The surge figure matters for motors, pumps, and compressors, which pull several times their running power for a moment. Compare the surge needed with the inverter's peak rating on its datasheet. The DC input current tells you how big your battery cables and fuses must be.
How It's Calculated
Continuous W = simultaneous AC running W × 1.25
Surge W = largest start surge (W × multiplier) + other simultaneous running W
DC amps = continuous W ÷ (system V × 0.92)
Worked Examples
Worked example · Pakistan, home with a water pump
Running together are a fridge at 150 W, three fans at 75 W each (225 W), lights at 60 W, and a pump at 750 W. Total = 1,185 W.
Continuous = 1,185 × 1.25 = 1,481 W, which rounds up to 1,500 W.
The pump has a start multiplier of 3, so its surge is 750 × 3 = 2,250 W.
Surge needed = 2,250 + (1,185 − 750) = 2,250 + 435 = 2,685 W.
On a 24 V system, DC amps = 1,500 ÷ (24 × 0.92) = 1,500 ÷ 22.08 = 67.9 A.
Worked example · Australia, off-grid workshop
Running together are a circular saw at 1,400 W, lights at 120 W, and a radio at 30 W. Total = 1,550 W.
Continuous = 1,550 × 1.25 = 1,937.5 W, which rounds up to 2,000 W.
The saw has a start multiplier of 2, so its surge is 1,400 × 2 = 2,800 W.
Surge needed = 2,800 + (1,550 − 1,400) = 2,800 + 150 = 2,950 W.
On a 48 V system, DC amps = 2,000 ÷ (48 × 0.92) = 2,000 ÷ 44.16 = 45.3 A.
Common Mistakes
- Adding every appliance in the house instead of the ones that run at the same time.
- Skipping the surge check for a pump, compressor, or air conditioner.
- Choosing a low-voltage inverter for a large load, which forces very heavy battery cable.
- Treating a modified sine wave inverter as safe for every motor and electronic charger.