Reading Your Result
The result is the time a full battery lasts at a steady load. It uses only the usable share of the bank, set by depth of discharge, so a 200 Ah lead-acid battery gives far less than 200 Ah of real runtime.
AC loads cost more than DC loads at the same label wattage, because the inverter draws extra from the battery to cover its own loss. Real runtime also falls when loads change or batteries age, so treat the number as an upper bound and leave some spare hours.
How It's Calculated
Hours = (V × Ah × DoD) ÷ load draw
Load draw = load W ÷ 0.92 for AC, or load W for DC
Worked Examples
Worked example · Pakistan, outage backup with LiFePO4
A 12 V, 200 Ah LiFePO4 battery has 12 × 200 = 2,400 Wh. Usable = 2,400 × 0.90 = 2,160 Wh.
The AC load is 300 W, so battery draw = 300 ÷ 0.92 = 326.1 W.
Runtime = 2,160 ÷ 326.1 = 6.62 hours.
That's about 6 hours and 37 minutes.
Worked example · Australia, camper trailer with AGM
A 24 V, 100 Ah AGM bank has 24 × 100 = 2,400 Wh. Usable = 2,400 × 0.50 = 1,200 Wh.
A 150 W DC compressor and light load draws 150 W with no inverter loss, so runtime = 1,200 ÷ 150 = 8.0 hours.
If the same 150 W ran through an inverter, draw = 150 ÷ 0.92 = 163.0 W.
Runtime would drop to 1,200 ÷ 163.0 = 7.36 hours.
Common Mistakes
- Entering the full Ah rating and ignoring depth of discharge.
- Using peak load watts instead of the average watts over the period.
- Forgetting that cold temperatures shrink usable capacity, especially in lead-acid.
- Skipping the inverter's idle draw when the load is small.