Reading Your Result
Solar panels make more voltage as they get colder. The label shows Voc at 25°C, but a frosty dawn can push it 10 to 20 percent higher. The result is the number to compare with the controller's max PV rating.
If cold Voc comes in below the limit, the string is safe on voltage. If it's over, remove a panel from the series string or move to a controller with a higher input rating. Going over the limit can destroy a controller, and it often voids the warranty.
How It's Calculated
Cold Voc = Voc × series × (1 + |coef %| ÷ 100 × (25 − lowest °C))
Cold Voc < controller max PV (75, 100, 150, 200, or 250 V)
Worked Examples
Worked example · Norway, mountain cabin
The panel has Voc 49.5 V and a −0.30 percent per °C coefficient. The lowest temperature is −20°C.
Cold factor = 1 + 0.003 × (25 + 20) = 1 + 0.135 = 1.135.
Cold Voc per panel = 49.5 × 1.135 = 56.2 V.
Four in series = 224.7 V, which fits a 250 V controller. Five in series = 280.9 V, which does not.
On a 150 V controller, 150 ÷ 56.2 = 2.67, so only 2 panels fit in series.
Worked example · Australia, frosty Tasmanian valley
The panel has Voc 38.0 V and a −0.28 percent per °C coefficient. The lowest temperature is −5°C.
Cold factor = 1 + 0.0028 × (25 + 5) = 1 + 0.084 = 1.084.
Cold Voc per panel = 38.0 × 1.084 = 41.2 V.
Three in series = 123.6 V, which fits a 150 V controller.
Four in series = 164.8 V, which exceeds 150 V, so keep the string to three panels.
Common Mistakes
- Using the coefficient for Pmax instead of the one for Voc. Pmax is usually larger, so the answer comes out too high.
- Using the average winter temperature rather than the record low for the site.
- Dropping the minus sign and getting a number that suggests voltage falls in the cold.
- Testing the string at the controller input using hot-day readings and assuming it's safe all year.