Reading Your Result
Start with the daily energy number. It's the total your system must make and store every day, with inverter losses added to AC loads only. Every other result builds on it, so a wrong load list throws off the whole design.
The array and battery results answer two different questions. The array tells you how much sun power you need on the worst month of the year, and the battery tells you how long you can run when the sun doesn't show. If one looks far larger than the other, check the days of autonomy and the sun hours before changing anything else.
How It's Calculated
Daily Wh = DC Wh + AC Wh ÷ 0.92
Array W = daily Wh ÷ (design sun hours × 0.80), panels = ceil(array W ÷ panel W)
Battery Wh = daily Wh × days ÷ (DoD × round-trip efficiency × temperature factor)
Worked Examples
Worked example · Pakistan, small home with fans and a fridge
Loads are 300 Wh of DC and 1,200 Wh of AC. Daily energy = 300 + 1,200 ÷ 0.92 = 300 + 1,304 = 1,604 Wh.
Assume 3.5 peak sun hours in the worst month. Array = 1,604 ÷ (3.5 × 0.80) = 1,604 ÷ 2.8 = 573 W.
With 400 W panels, 573 ÷ 400 = 1.43, which rounds up to 2 panels (800 W).
For LiFePO4 at 25°C and 1 day of autonomy, battery = 1,604 ÷ (0.90 × 0.95) = 1,604 ÷ 0.855 = 1,876 Wh.
At 12 V, 1,876 ÷ 12 = 156 Ah, so a 160 Ah battery works.
Worked example · Norway, summer cabin
Loads are 200 Wh of DC and 800 Wh of AC. Daily energy = 200 + 800 ÷ 0.92 = 200 + 870 = 1,070 Wh.
The cabin is used May to September. Assume 3.0 peak sun hours in the worst of those months. Array = 1,070 ÷ (3.0 × 0.80) = 1,070 ÷ 2.4 = 446 W.
With 300 W panels, 446 ÷ 300 = 1.49, which rounds up to 2 panels (600 W).
For AGM at 10°C with 2 days of autonomy, battery = 1,070 × 2 ÷ (0.50 × 0.85 × 0.90) = 2,140 ÷ 0.3825 = 5,595 Wh.
At 12 V, 5,595 ÷ 12 = 466 Ah, so a 470 Ah bank is the next practical size.
Common Mistakes
- Using the yearly average sun hours instead of the worst month, which leaves the system short for several months of the year.
- Adding inverter loss to DC loads, which inflates the daily figure and oversizes everything.
- Forgetting loads that run only part of the day, such as a fridge compressor, and entering the full 24 hours.
- Sizing the battery without checking the lowest temperature at the site.