Reading Your Result
Voltage drop is energy lost as heat in the cable. The result shows it as a percent of circuit voltage, and the limits are 2 percent from panels to controller and 3 percent from battery to inverter. If your number is higher, use thicker wire, shorten the run, or raise the circuit voltage.
Voltage drop is only half the job. A wire that passes the drop test may still be too thin to carry the current safely, so compare the result with the ampacity tables in your local electrical code. Use the larger size when the two disagree.
How It's Calculated
Drop % = (2 × one-way length m × current A × 0.0172 ÷ area mm²) ÷ system V × 100
mm² 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95. AWG 14 = 2.08, 12 = 3.31, 10 = 5.26, 8 = 8.37, 6 = 13.3, 4 = 21.2, 2 = 33.6, 1/0 = 53.5 mm²
Fuse = 1.25 × current, rounded up to 1, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 100, 125, 150, 175, 200, 225, 250, 300, or 400 A
Worked Examples
Worked example · Arizona, USA, panel run in AWG
A string makes 8 A at 96 V over an 18 m one-way run. The limit is 2 percent.
Try 14 AWG (2.08 mm²). Drop = 2 × 18 × 8 × 0.0172 ÷ 2.08 = 4.954 ÷ 2.08 = 2.38 V, and 2.38 ÷ 96 = 2.48 percent. That fails.
Try 12 AWG (3.31 mm²). Drop = 4.954 ÷ 3.31 = 1.50 V, and 1.50 ÷ 96 = 1.56 percent. That passes.
Fuse = 1.25 × 8 = 10 A, which is already a standard size.
Worked example · Norway, battery to inverter
A 2,000 W inverter on a 24 V bank draws 2,000 ÷ (24 × 0.92) = 90.6 A. The run is 1.5 m one way, and the limit is 3 percent.
Try 10 mm². Drop = 2 × 1.5 × 90.6 × 0.0172 ÷ 10 = 0.467 V, and 0.467 ÷ 24 = 1.95 percent. That passes the drop test.
At 90.6 A, 10 mm² is far too thin for heat limits, so check ampacity and step up. At 25 mm², drop = 0.187 V, which is 0.78 percent.
Fuse = 1.25 × 90.6 = 113 A, which rounds up to 125 A.
Common Mistakes
- Entering the round-trip length instead of the one-way length. The formula already doubles it.
- Choosing wire only by the drop test and skipping the ampacity table.
- Using a fuse that's larger than the wire can handle.
- Running low-voltage panel wiring with one thin cable to save money, then losing a visible share of power every sunny day.